Basic Rules for Installation
- AIR TERMIALS MUST BE LOCATED WITHIN 2' OF AND OUTSIDE CORNER OR RIDGE END
- AIR TERMINALS MUST BE SPACED 20' APART MAXIMUM
- CABLE MUST BE FASTENED 36" O.C. MAX
- CABLE BENDS SHALL NOT BE LESS THAT AN 8" RADIUS
- CABLES SHALL BE RUN HORIZONTAL OR IN A DOWNWARD PATH TO GROUND . IF A CABLE MUST BE RUN UPHILL IT MUST BE RUN AT A 1/4" SLOPE OR LESS
- METAL BODIES SUCH AS: ATTIC VENTS, VENTS THRU THE ROOF, GUTTERS, ETC. LOCATED WITHIN 6' OF THE MAIN LIGHTNING PROTECTION CABLE MUST BE BONDED TO THE SYSTEM WITH SECONDARY MATERIAL MINIMUM
- ALL METAL BODIES THAT ARE HIGHER THAN THE LIGHNTING RODS MUST BE BONDED TO THE LIGHTNING PROTECTION SYSTEM MUST BE BONDED TO THE FULL SIZE CABLE
- ALL ANTENNAS, SATALITE DISHES, ETC. MUST BE BONDED TO THE SYSTEM WITH A MAIN LIGHTNING PROTECTION CABLE.
- THERE MUST BE A GROUND ROD FOR EVERY 100' OF PERIMETER SURROUNDING THE STRUCTURE.
EXAMPLE - 627' PERIMETER NEEDS 7 GROUND RODS
EXAMPLE - 701' PERIMETER NEEDS 8 GROUND RODS
EXAMPLE - 800' PERIMETER NEEDS 8 GROUND RODS